Product Code | MSD-30 |
---|---|
Description | Cooling Tower - MSD-30 CFB - 139 Kw |
Unit | Each |
Notes | Mesan Cooling Tower Design conditions - Pressure - 99.4 Kpa Wet bulb temperature - +27c Dry bulb temperature - +32c Inlet water temperature - +37c Outlet water temperature - +32c Water flow rate (+27 wet bulb) - 24 m3/h Heat rejection at above conditions - 139 Kw/h Cooling tower diameter - 1615 mm Cooling tower height - 1885 mm Fan diameter - 884mm Fan power consumption - 0.75 Kw Air flow - 14400 m3/h Weight (Dry / Wet) - 150 Kg / 355 Kg Sound power level (10 meters) - 55.3 DBA |
Image | |
Web URL | http://www.mesanct.com/ |
Documents |