Split Cond Valve - Sporlan - 12D13B-SC - 1-5/8"




 Product Code  3784-00
 Description  Split Cond Valve - Sporlan - 12D13B-SC - 1-5/8"
 Unit  Each
 Notes The split condenser valve is a relatively simple modification of the standard heat reclaim
valve. The upper seat and port of the split condenser valve opens and closes.
The lower port is always open. During the normal full condenser mode, the refrigerant
flow is split evenly between the two halves of the condenser. When employing heat
reclaim in series with the outdoor condenser of a refrigeration system, the required
refrigerant charge may be a potential problem. If a majority or all of the heat is removed
from the refrigerant in the heat reclaim coil, some or all of the refrigerant may be in the
form of liquid when it enters the outdoor condenser coil.

During this condition, the liquid charge in the system would have to be large enough
to completely fill the condenser with liquid. The requirement for this charge may be
reduced by splitting and using only half of the outdoor condenser. During the winter
the effectiveness of the condenser surface area is much greater than it is during the
summer. Typically, split condenser valves are controlled by an ambient temperature
control set for a specific outdoor temperature. This usually coincides with the
requirement for heat reclaim in the building. In some applications, the control system
will also split the condenser anytime the heat reclaim coil is active.

Connections - 1-5/8" ODS
Maximum working pressure - 31 bar

Solenoid coil assembly sold separately
Coil type - MKC-1