Product Code | 3784-00 |
---|---|
Description | Split Cond Valve - Sporlan - 12D13B-SC - 1-5/8" |
Unit | Each |
Notes | The split condenser valve is a relatively simple modification of the standard heat reclaim valve. The upper seat and port of the split condenser valve opens and closes. The lower port is always open. During the normal full condenser mode, the refrigerant flow is split evenly between the two halves of the condenser. When employing heat reclaim in series with the outdoor condenser of a refrigeration system, the required refrigerant charge may be a potential problem. If a majority or all of the heat is removed from the refrigerant in the heat reclaim coil, some or all of the refrigerant may be in the form of liquid when it enters the outdoor condenser coil. During this condition, the liquid charge in the system would have to be large enough to completely fill the condenser with liquid. The requirement for this charge may be reduced by splitting and using only half of the outdoor condenser. During the winter the effectiveness of the condenser surface area is much greater than it is during the summer. Typically, split condenser valves are controlled by an ambient temperature control set for a specific outdoor temperature. This usually coincides with the requirement for heat reclaim in the building. In some applications, the control system will also split the condenser anytime the heat reclaim coil is active. Connections - 1-5/8" ODS Maximum working pressure - 31 bar Solenoid coil assembly sold separately Coil type - MKC-1 |
Image | |
Web URL | http://sporlanonline.com/ |