ORD-4-20 - 7/8" ODS




 Product Code  902878
 Description  ORD-4-20 - 7/8" ODS
 Unit  Each
 Notes The ORD valve is a pressure differential valve that responds to changes in the pressure
difference across the valve, Figure 6 on the next page. The valve designation stands for
Opens on Rise of Differential pressure. Therefore, the ORD is dependent on some other
control valve or action for its operation. And in this respect, it is used with the ORI for
head pressure control. As the ORI valve starts to throttle the flow of liquid refrigerant
from the condenser, a pressure differential is created across the ORD. When the
differential reaches setpoint, the ORD starts to open and bypasses hot gas to the liquid
drain line. As the differential increases, the ORD opens further until its full stroke is
reached at a differential of 10 psi above setpoint. Due to its function in the control of
head pressure, the full stroke can be utilized in selecting the ORD. The standard
pressure setting for the ORD is 20 psig. ORD type valve is used in conjunction with
ORI type valve.

Connections - 7/8" ODS

Maximum working pressure - 31 bar

ORI valve sold separately.
 Image Image
 Web URL http://sporlanonline.com/
 Documents
© Copyright 2016 Cooling Equipment Ltd. All rights reserved. Site by Spire.